GroundGridLab · IEC 60364 · NEC 250 context
Long outbuilding circuit
A long phase and CPC run makes the circuit resistances dominate the upstream contribution. The branch is close to the trip threshold.
Device threshold shortfall. Compared with the pickup for the selected protective device.
- Fault loop impedance
- 2.073 Ω
- Earth-fault current
- 105.4 A
- Maximum permissible Zₛ
- 1.748 Ω
- CPC area at modeled current
- 0.57967 mm²
Inputs
| Earthing arrangement | TN-C-S |
|---|---|
| Nominal line-to-earth U₀ | 230 V |
| Minimum voltage factor | 0.95 × |
| External impedance Zₑ | 0.24 Ω |
| Phase resistance R₁ | 0.65 Ω |
| CPC resistance R₂ | 0.76 Ω |
| Resistance temperature factor | 1.3 × |
| Protective device | B curve · 5 × In |
| Breaker rated current In | 25 A |
| Clearing / design time | 0.4 s |
| Protective conductor k | 115 A√s/mm² |
Derived values
| Protective device threshold | 125 A |
|---|---|
| Zₛ headroom | -0.325 Ω |
| Fault current above threshold | -19.597 A |
| Warm phase / CPC resistance | 0.845 Ω / 0.988 Ω |
| Next size for modeled fault duty | 0.75 mm² |
| Supply voltage after cₘᵢₙ | 218.5 V |
Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.