GroundGridLab · IEC 60364 · NEC 250 context
Type D motor feeder
A motor branch uses a high magnetic pickup to tolerate inrush. The higher trip multiple reduces the maximum acceptable loop impedance.
Device threshold shortfall. Compared with the pickup for the selected protective device.
- Fault loop impedance
- 0.674 Ω
- Earth-fault current
- 324.18 A
- Maximum permissible Zₛ
- 0.34141 Ω
- CPC area at modeled current
- 1.0138 mm²
Inputs
| Earthing arrangement | TN-S |
|---|---|
| Nominal line-to-earth U₀ | 230 V |
| Minimum voltage factor | 0.95 × |
| External impedance Zₑ | 0.17 Ω |
| Phase resistance R₁ | 0.18 Ω |
| CPC resistance R₂ | 0.24 Ω |
| Resistance temperature factor | 1.2 × |
| Protective device | D curve · 20 × In |
| Breaker rated current In | 32 A |
| Clearing / design time | 0.2 s |
| Protective conductor k | 143 A√s/mm² |
Derived values
| Protective device threshold | 640 A |
|---|---|
| Zₛ headroom | -0.33259 Ω |
| Fault current above threshold | -315.82 A |
| Warm phase / CPC resistance | 0.216 Ω / 0.288 Ω |
| Next size for modeled fault duty | 1.5 mm² |
| Supply voltage after cₘᵢₙ | 218.5 V |
Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.