GroundGridLab · IEEE 80-2013 · Onderdonk
Aluminum alloy ground lead
A short above-grade aluminum lead is examined for fault heating. The example uses 5005-H19 material constants and an assumed terminal temperature.
Candidate meets thermal area. The comparison uses the selected limit for Aluminum 5005-H19.
- Minimum cross-section
- 79.231 mm²
- Next standard size
- 95 mm²
- Candidate utilization
- 52.821 %
- Joint / material limit
- 632 °C
Inputs
| Material / connection | Aluminum 5005-H19 |
|---|---|
| Starting conductor temperature | 50 °C |
| Candidate cross-section | 150 mm² |
| Equivalent RMS conductor current | 16 kA |
| Fault clearing time | 0.55 s |
Derived values
| Minimum in both systems | 79.231 mm² / 156.36 kcmil |
|---|---|
| Next metric size | 95 mm² |
| Next AWG / kcmil size | 3/0 AWG |
| Candidate time at entered current | 1.9713 s |
| Candidate current at entered time | 30.291 kA |
| Thermal I²t utilization | 27.9 % |
| Reference resistivity | 3.2227 μΩ·cm |
| Volumetric heat capacity | 2.43 J/(cm³·°C) |
Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.