Worked example · IEEE 80-2013 · Onderdonk

Aluminum alloy ground lead

Adiabatic fault-current sizing of ground conductors using material constants and joint temperature limits.

A short above-grade aluminum lead is examined for fault heating. The example uses 5005-H19 material constants and an assumed terminal temperature.

Candidate meets thermal area

The comparison uses the selected limit for Aluminum 5005-H19.

Minimum cross-section
79.231 mm²
Next standard size
95 mm²
Candidate utilization
52.821 %
Joint / material limit
632 °C

Inputs

Conductor and joint
°C
mm²
Fault duty
kA
s

Time–current thermal curves

Live schematic
Min. area79.23 mm²Next size95 mm²Utilization52.82 %Temp limit632 °CFUSING TIME / s0.09811.9337.85.331648RMS fault current / kACONDUCTOR CROSS-SECTIONSCandidateMinimum thermal area150 mm²79.23 mm²120 mm²185 mm²Required / candidate area52.82%
Logarithmic axes. The candidate curve and two standard-size references use equal material, joint and initial temperature.

Derived values & comparisons
Minimum in both systems79.231 mm² / 156.36 kcmil
Next metric size95 mm²
Next AWG / kcmil size3/0 AWG
Candidate time at entered current1.9713 s
Candidate current at entered time30.291 kA
Thermal I²t utilization27.9 %
Reference resistivity3.2227 μΩ·cm
Volumetric heat capacity2.43 J/(cm³·°C)

Screening scope. Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.

Try this. Compare the alloy with the EC-0 aluminum preset for the same candidate area and fault duty.

Calculation method

IEEE Std 80-2013 §11.3.1, equations 45–46 and Tables 1–2. IEEE Eq. 45 gives mm² from kA, seconds, TCAP in J/(cm³·°C), ρᵣ in μΩ·cm, and Celsius temperatures. The result is converted to kcmil using 1 kcmil = 0.506707479 mm².

The log term is ln[(K₀ + Tₘ)/(K₀ + Tₐ)]. The candidate utilization is required area / entered area. The thermal-energy utilization is its square. Standard sizes round up from the unrounded area.

The brazed and bolted connection caps are screening settings. Aluminum EC-0 and 5005-H19 resistivity and temperature coefficients come from NBS Handbook 109, Table 1. The aluminum heat capacity and lower melting limits are engineering approximations. Zinc-coated rod constants serve as a galvanized-steel proxy.

Standards and model assumptions