GroundGridLab · IEEE 80-2013 · Onderdonk
Copper-clad steel Annex benchmark
IEEE 80 §11.3.1 gives an example of a 30% copper-clad steel conductor subjected to 1 kA for 1 s at 40 °C.
Candidate meets thermal area. The comparison uses the selected limit for Copper-clad steel · 30%.
- Minimum cross-section
- 6.1129 mm²
- Next standard size
- 10 mm²
- Candidate utilization
- 61.129 %
- Joint / material limit
- 1,084 °C
Inputs
| Material / connection | Copper-clad steel · 30% |
|---|---|
| Starting conductor temperature | 40 °C |
| Candidate cross-section | 10 mm² |
| Equivalent RMS conductor current | 1 kA |
| Fault clearing time | 1 s |
Derived values
| Minimum in both systems | 6.1129 mm² / 12.064 kcmil |
|---|---|
| Next metric size | 10 mm² |
| Next AWG / kcmil size | 9 AWG |
| Candidate time at entered current | 2.6761 s |
| Candidate current at entered time | 1.6359 kA |
| Thermal I²t utilization | 37.368 % |
| Reference resistivity | 5.86 μΩ·cm |
| Volumetric heat capacity | 3.85 J/(cm³·°C) |
Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.