Worked example · IEEE 80-2013 · Onderdonk

Galvanized steel bond

Adiabatic fault-current sizing of ground conductors using material constants and joint temperature limits.

A zinc-coated steel bond is screened with the coating temperature as the governing cap. The material preset represents a zinc-coated steel rod proxy.

Candidate meets thermal area

The comparison uses the selected limit for Galvanized steel · zinc limit.

Minimum cross-section
98.823 mm²
Next standard size
120 mm²
Candidate utilization
53.418 %
Joint / material limit
419 °C

Inputs

Conductor and joint
°C
mm²
Fault duty
kA
s

Time–current thermal curves

Live schematic
Min. area98.82 mm²Next size120 mm²Utilization53.42 %Temp limit419 °CFUSING TIME / s0.08061.6433.43.331030RMS fault current / kACONDUCTOR CROSS-SECTIONSCandidateMinimum thermal area185 mm²98.82 mm²150 mm²240 mm²Required / candidate area53.42%
Logarithmic axes. The candidate curve and two standard-size references use equal material, joint and initial temperature.

Derived values & comparisons
Minimum in both systems98.823 mm² / 195.03 kcmil
Next metric size120 mm²
Next AWG / kcmil size4/0 AWG
Candidate time at entered current1.577 s
Candidate current at entered time18.72 kA
Thermal I²t utilization28.535 %
Reference resistivity20.1 μΩ·cm
Volumetric heat capacity3.9 J/(cm³·°C)

Screening scope. Verify the tested connection limit, actual equivalent RMS current, fault duty, corrosion allowance and mechanical minimum. Use these checks together to specify the conductor.

Try this. Compare the candidate area with the next metric size and confirm the actual product specification before applying the result.

Calculation method

IEEE Std 80-2013 §11.3.1, equations 45–46 and Tables 1–2. IEEE Eq. 45 gives mm² from kA, seconds, TCAP in J/(cm³·°C), ρᵣ in μΩ·cm, and Celsius temperatures. The result is converted to kcmil using 1 kcmil = 0.506707479 mm².

The log term is ln[(K₀ + Tₘ)/(K₀ + Tₐ)]. The candidate utilization is required area / entered area. The thermal-energy utilization is its square. Standard sizes round up from the unrounded area.

The brazed and bolted connection caps are screening settings. Aluminum EC-0 and 5005-H19 resistivity and temperature coefficients come from NBS Handbook 109, Table 1. The aluminum heat capacity and lower melting limits are engineering approximations. Zinc-coated rod constants serve as a galvanized-steel proxy.

Standards and model assumptions