GroundGridLab · Dwight · uniform soil
Ground Rod Array Calculator
Vertical electrode resistance with optional backfill and mutual coupling between rods.
Resistance above target. The first count meeting the target in this layout is 6.
- Array resistance
- 13.019 Ω
- Single-rod resistance
- 40.191 Ω
- Array utilization
- 77.179 %
- Rods to reach target
- 6 rods
Inputs
| Native soil resistivity | 120 Ω·m |
|---|---|
| Driven rod length | 3 m |
| Rod radius | 8 mm |
| Backfill sleeve thickness | 0 mm |
| Rod layout | In-line row |
| Number of rods | 4 rods |
| Minimum rod centers | 3 m |
| Array resistance target | 10 Ω |
Derived values
| Bare single rod | 40.191 Ω |
|---|---|
| Ideal uncoupled array | 10.048 Ω |
| Coupling factor vs. ideal | 1.2957 × |
| Center spacing / driven length | 1 × |
| Effective sleeve diameter | 16 mm |
| Maximum modeled count | 128 rods |
The sleeve is an ideal full-length cylinder. Uniform soil, perfect bonding and equal rod currents are assumed. Use field resistance tests and a layered model for design.