Worked example · IEEE 80-2013

Annex B example exposure limits

Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.

IEEE 80 Annex B.1 uses a 70 kg criterion for a restricted yard with 400 Ω·m native soil, a 102 mm surface layer and a half-second exposure.

Voltage limit exceeded

At least one candidate exceeds its limit at the entered duration.

Permissible touch
840.55 V
Permissible step
2,696.1 V
Surface factor Cₛ
0.74286
Clearing headroom
-0.14822 s

Inputs

Exposure
s
Surface
Ω·m
mm
Enter 0 for bare earth.
Ω·m
Candidate voltages
V
V

Surface section & body paths

Live schematic
Touch limit840.5 VStep limit2,696 VSurface Cₛ0.7429Time margin-0.1482 sSOIL SECTIONCover 102 mmNative 400 Ω·mEQUIVALENT RESISTANCETouch · feet parallelStep · feet in seriesR body + R foot / 2R body + 2 × R foot1,002 V applied600 V appliedTouch / limit119.2%Step / limit22.25%
Schematic section. Step exposure uses two foot resistances in series. Touch uses two in parallel.

Derived values & comparisons
Touch comparison at 70 kgFail
Step comparison at 70 kgPass
Effective contact resistivity1,857.1 Ω·m
Allowable body current222.03 mA
Maximum clearing duration in model range0.3518 s
50 kg touch / step621 V / 1,992 V
70 kg touch / step840.5 V / 2,696 V

Screening scope. Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.

Try this. Compare the unrounded cover-factor result with Annex B’s hand-rounded step and touch limits.

Calculation method

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Standards and model assumptions