Worked example · IEEE 80-2013

Bare-earth access track

Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.

A route beside a yard has no insulating surface cover. Use the native soil and the 50 kg exposure model near the accessible boundary.

Voltage limit exceeded

At least one candidate exceeds its limit at the entered duration.

Permissible touch
221.08 V
Permissible step
296.07 V
Surface factor Cₛ
1
Clearing headroom
-0.19152 s

Inputs

Exposure
s
Surface
Ω·m
mm
Enter 0 for bare earth.
Candidate voltages
V
V

Surface section & body paths

Live schematic
Touch limit221.1 VStep limit296.1 VSurface Cₛ1Time margin-0.1915 sSOIL SECTIONBare earthNative 85 Ω·mEQUIVALENT RESISTANCETouch · feet parallelStep · feet in seriesR body + R foot / 2R body + 2 × R foot240 V applied440 V appliedTouch / limit108.6%Step / limit148.6%
Schematic section. Step exposure uses two foot resistances in series. Touch uses two in parallel.

Derived values & comparisons
Touch comparison at 50 kgFail
Step comparison at 50 kgFail
Effective contact resistivity85 Ω·m
Allowable body current196.08 mA
Maximum clearing duration in model range0.1585 s
50 kg touch / step221.1 V / 296.1 V
70 kg touch / step299.2 V / 400.7 V

Screening scope. Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.

Try this. Add 50 mm of a specified high-resistivity cover and compare both permissible voltages.

Calculation method

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Standards and model assumptions