GroundGridLab · IEEE 80-2013
Wet limestone over clay
Winter moisture reduces the effective resistivity of a thin limestone layer. The touch estimate comes from a separate grid calculation.
Voltage limit exceeded. At least one candidate exceeds its limit at the entered duration.
- Permissible touch
- 333.09 V
- Permissible step
- 813.6 V
- Surface factor Cₛ
- 0.6175
- Clearing headroom
- -0.20382 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 0.45 s |
| Native soil resistivity | 65 Ω·m |
| Surface layer thickness | 65 mm |
| Surface material resistivity | 1,000 Ω·m |
| Mesh / touch voltage | 430 V |
| Step voltage | 1,100 V |
Derived values
| Touch comparison at 50 kg | Fail |
|---|---|
| Step comparison at 50 kg | Fail |
| Effective contact resistivity | 617.5 Ω·m |
| Allowable body current | 172.92 mA |
| Maximum clearing duration in model range | 0.2462 s |
| 50 kg touch / step | 333.1 V / 813.6 V |
| 70 kg touch / step | 450.8 V / 1,101 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.