GroundGridLab · IEEE 80-2013
Bare-earth access track
A route beside a yard has no insulating surface cover. Use the native soil and the 50 kg exposure model near the accessible boundary.
Voltage limit exceeded. At least one candidate exceeds its limit at the entered duration.
- Permissible touch
- 221.08 V
- Permissible step
- 296.07 V
- Surface factor Cₛ
- 1
- Clearing headroom
- -0.19152 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 0.35 s |
| Native soil resistivity | 85 Ω·m |
| Surface layer thickness | 0 mm |
| Mesh / touch voltage | 240 V |
| Step voltage | 440 V |
Derived values
| Touch comparison at 50 kg | Fail |
|---|---|
| Step comparison at 50 kg | Fail |
| Effective contact resistivity | 85 Ω·m |
| Allowable body current | 196.08 mA |
| Maximum clearing duration in model range | 0.1585 s |
| 50 kg touch / step | 221.1 V / 296.1 V |
| 70 kg touch / step | 299.2 V / 400.7 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.