GroundGridLab · IEEE 80-2013
Conductive overlay over dry fill
A damp overlay is less resistive than the material below it. A formal contact-resistance factor alone does not account for redistributed surface currents.
Surface model review. Both candidate voltages are within the selected exposure limits. The cover is more conductive than native soil. Surface voltages can redistribute.
- Permissible touch
- 260.79 V
- Permissible step
- 492.92 V
- Surface factor Cₛ
- 3.125
- Clearing headroom
- 0.11426 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 0.4 s |
| Native soil resistivity | 600 Ω·m |
| Surface layer thickness | 75 mm |
| Surface material resistivity | 90 Ω·m |
| Mesh / touch voltage | 230 V |
| Step voltage | 430 V |
Derived values
| Touch comparison at 50 kg | Pass |
|---|---|
| Step comparison at 50 kg | Pass |
| Effective contact resistivity | 281.25 Ω·m |
| Allowable body current | 183.41 mA |
| Maximum clearing duration in model range | 0.5143 s |
| 50 kg touch / step | 260.8 V / 492.9 V |
| 70 kg touch / step | 353 V / 667.1 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.