Worked example · IEEE 80-2013

Conductive overlay over dry fill

Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.

A damp overlay is less resistive than the material below it. A formal contact-resistance factor alone does not account for redistributed surface currents.

Surface model review

Both candidate voltages are within the selected exposure limits. The cover is more conductive than native soil. Surface voltages can redistribute.

Permissible touch
260.79 V
Permissible step
492.92 V
Surface factor Cₛ
3.125
Clearing headroom
0.11426 s

Inputs

Exposure
s
Surface
Ω·m
mm
Enter 0 for bare earth.
Ω·m
Candidate voltages
V
V

Surface section & body paths

Live schematic
Touch limit260.8 VStep limit492.9 VSurface Cₛ3.125Time margin0.1143 sSOIL SECTIONCover 75 mmNative 600 Ω·mEQUIVALENT RESISTANCETouch · feet parallelStep · feet in seriesR body + R foot / 2R body + 2 × R foot230 V applied430 V appliedTouch / limit88.19%Step / limit87.24%
Schematic section. Step exposure uses two foot resistances in series. Touch uses two in parallel.

Derived values & comparisons
Touch comparison at 50 kgPass
Step comparison at 50 kgPass
Effective contact resistivity281.25 Ω·m
Allowable body current183.41 mA
Maximum clearing duration in model range0.5143 s
50 kg touch / step260.8 V / 492.9 V
70 kg touch / step353 V / 667.1 V

Screening scope. Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.

Try this. Inspect the review flag and compare the result with an equal-resistivity overlay.

Calculation method

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Standards and model assumptions