GroundGridLab · IEEE 80-2013
Delayed backup breaker clearing
A failed primary trip leaves the backup clearing time in control. A voltage pair that was within the fast-clearing limit can exceed it under backup.
Voltage limit exceeded. At least one candidate exceeds its limit at the entered duration.
- Permissible touch
- 381.06 V
- Permissible step
- 1,219 V
- Surface factor Cₛ
- 0.70398
- Clearing headroom
- -0.75771 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 1.3 s |
| Native soil resistivity | 120 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 2,600 Ω·m |
| Mesh / touch voltage | 590 V |
| Step voltage | 950 V |
Derived values
| Touch comparison at 50 kg | Fail |
|---|---|
| Step comparison at 50 kg | Pass |
| Effective contact resistivity | 1,830.3 Ω·m |
| Allowable body current | 101.74 mA |
| Maximum clearing duration in model range | 0.5423 s |
| 50 kg touch / step | 381.1 V / 1,219 V |
| 70 kg touch / step | 515.8 V / 1,650 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.