Worked example · IEEE 80-2013

Delayed backup breaker clearing

Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.

A failed primary trip leaves the backup clearing time in control. A voltage pair that was within the fast-clearing limit can exceed it under backup.

Voltage limit exceeded

At least one candidate exceeds its limit at the entered duration.

Permissible touch
381.06 V
Permissible step
1,219 V
Surface factor Cₛ
0.70398
Clearing headroom
-0.75771 s

Inputs

Exposure
s
Surface
Ω·m
mm
Enter 0 for bare earth.
Ω·m
Candidate voltages
V
V

Surface section & body paths

Live schematic
Touch limit381.1 VStep limit1,219 VSurface Cₛ0.704Time margin-0.7577 sSOIL SECTIONCover 100 mmNative 120 Ω·mEQUIVALENT RESISTANCETouch · feet parallelStep · feet in seriesR body + R foot / 2R body + 2 × R foot590 V applied950 V appliedTouch / limit154.8%Step / limit77.93%
Schematic section. Step exposure uses two foot resistances in series. Touch uses two in parallel.

Derived values & comparisons
Touch comparison at 50 kgFail
Step comparison at 50 kgPass
Effective contact resistivity1,830.3 Ω·m
Allowable body current101.74 mA
Maximum clearing duration in model range0.5423 s
50 kg touch / step381.1 V / 1,219 V
70 kg touch / step515.8 V / 1,650 V

Screening scope. Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.

Try this. Change the exposure duration from 1.3 s to 0.3 s and track the change in the margins.

Calculation method

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Standards and model assumptions