GroundGridLab · IEEE 80-2013
Partial gravel washout
Runoff leaves only a shallow gravel layer beside a steel operating handle. Treat the measured residual thickness as a sensitivity case.
Voltage limit exceeded. At least one candidate exceeds its limit at the entered duration.
- Permissible touch
- 404.81 V
- Permissible step
- 1,170 V
- Surface factor Cₛ
- 0.36627
- Clearing headroom
- -0.13533 s
Inputs
| Body weight model | 50 kg / 110 lb |
|---|---|
| Shock / clearing duration | 0.6 s |
| Native soil resistivity | 175 Ω·m |
| Surface layer thickness | 22 mm |
| Surface material resistivity | 3,100 Ω·m |
| Mesh / touch voltage | 460 V |
| Step voltage | 740 V |
Derived values
| Touch comparison at 50 kg | Fail |
|---|---|
| Step comparison at 50 kg | Pass |
| Effective contact resistivity | 1,135.4 Ω·m |
| Allowable body current | 149.76 mA |
| Maximum clearing duration in model range | 0.4647 s |
| 50 kg touch / step | 404.8 V / 1,170 V |
| 70 kg touch / step | 547.9 V / 1,584 V |
Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.