Worked example · IEEE 80-2013

Partial gravel washout

Permissible voltage for a person standing on soil or a surface layer during an AC ground fault.

Runoff leaves only a shallow gravel layer beside a steel operating handle. Treat the measured residual thickness as a sensitivity case.

Voltage limit exceeded

At least one candidate exceeds its limit at the entered duration.

Permissible touch
404.81 V
Permissible step
1,170 V
Surface factor Cₛ
0.36627
Clearing headroom
-0.13533 s

Inputs

Exposure
s
Surface
Ω·m
mm
Enter 0 for bare earth.
Ω·m
Candidate voltages
V
V

Surface section & body paths

Live schematic
Touch limit404.8 VStep limit1,170 VSurface Cₛ0.3663Time margin-0.1353 sSOIL SECTIONCover 22 mmNative 175 Ω·mEQUIVALENT RESISTANCETouch · feet parallelStep · feet in seriesR body + R foot / 2R body + 2 × R foot460 V applied740 V appliedTouch / limit113.6%Step / limit63.25%
Schematic section. Step exposure uses two foot resistances in series. Touch uses two in parallel.

Derived values & comparisons
Touch comparison at 50 kgFail
Step comparison at 50 kgPass
Effective contact resistivity1,135.4 Ω·m
Allowable body current149.76 mA
Maximum clearing duration in model range0.4647 s
50 kg touch / step404.8 V / 1,170 V
70 kg touch / step547.9 V / 1,584 V

Screening scope. Use the worse site conditions and the appropriate body-weight criterion. This screen covers 0.03–3 s power-frequency exposure and excludes transferred or metal-to-metal touch voltage.

Try this. Set the cover to zero to represent the most exposed patch along the handle approach.

Calculation method

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Standards and model assumptions