NFPA 150-foot sphere
The plan calls for a 150 ft sphere. Using the exact conversion preserves the stated NFPA geometry when switching to US units.
Clearance checks met. Compare centerline clearance and the available separation against the simplified model.
- Sphere radius
- 45.72 m
- Single-mast reach
- 9.8415 m
- Midspan clearance
- 5.5141 m
- Required separation
- 0.24 m
Inputs
| Lightning protection level | NFPA 780 · 150 ft |
|---|---|
| Equal mast height | 13.716 m |
| Object height above datum | 6.096 m |
| Mast center spacing | 27.432 m |
| LPS factor kᵢ | 0.04 × |
| Current sharing k꜀ | 0.5 × |
| Insulating material kₘ | 1 × |
| Length to bonding point | 12 m |
| Available separation | 0.8 m |
Derived values
| Midspan sag | 2.1059 m |
|---|---|
| Midspan envelope height | 11.61 m |
| Single mast effective height | 13.716 m |
| Span must be below | 91.44 m |
| Separation margin | 0.56 m |
| Lightning protection factor kᵢ | 0.04 × |
Evaluate the whole site in 3D, including roof edges, sides, other strike points and current paths. The separation-distance screen uses simplified IEC factors.