GroundGridLab · IEC 62305-3 · NFPA 780
Mast taller than the sphere radius
A tall mast exceeds the rolling sphere’s radius. The single-mast side reach is capped at the sphere radius in the simple section.
Clearance checks met. Single-mast reach uses the sphere-radius cap. The dual-mast section uses the actual tips.
- Sphere radius
- 20 m
- Single-mast reach
- 1.6697 m
- Midspan clearance
- 14.321 m
- Required separation
- 0.88 m
Inputs
| Lightning protection level | IEC LPL I |
|---|---|
| Equal mast height | 29 m |
| Object height above datum | 12 m |
| Mast center spacing | 20 m |
| Current sharing k꜀ | 0.5 × |
| Insulating material kₘ | 1 × |
| Length to bonding point | 22 m |
| Available separation | 1.1 m |
Derived values
| Midspan sag | 2.6795 m |
|---|---|
| Midspan envelope height | 26.321 m |
| Single mast effective height | 20 m |
| Span must be below | 40 m |
| Separation margin | 0.22 m |
| Lightning protection factor kᵢ | 0.08 × |
Evaluate the whole site in 3D, including roof edges, sides, other strike points and current paths. The separation-distance screen uses simplified IEC factors.