GroundGridLab · IEEE 80-2013
IEEE 80 Annex B square grid
The first Annex B design uses a 70 × 70 m grid with 7 m pitch, 0.5 m burial and no rods. The maximum grid current is based on the 3.18 kA bus fault and a 0.6 split.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 2.7757 Ω
- Ground potential rise
- 5,296 V
- Corner mesh voltage
- 1,001.6 V
- Corner step voltage
- 609.73 V
Inputs
| Grid length | 70 m |
|---|---|
| Grid width | 70 m |
| Maximum mesh pitch | 7 m |
| Burial depth | 0.5 m |
| Conductor diameter | 10 mm |
| Total rod length | 0 m |
| Symmetrical ground fault | 3.18 kA |
| Current split factor | 0.6 × |
| Decrement factor | 1 × |
| Native soil resistivity | 400 Ω·m |
| Surface layer thickness | 102 mm |
| Surface material resistivity | 2,500 Ω·m |
| Body weight model | 70 kg / 154 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 2.7918 Ω |
|---|---|
| Circular plate reference | 2.5321 Ω |
| Maximum earth current Iɢ | 1.908 kA |
| Grid area | 4,900 m² |
| Horizontal / total buried length | 1,540 m / 1,540 m |
| Mesh bay count | 10 × 10 |
| Fitted pitches | 7 m × 7 m |
| Kₘ / Kᵢ / Kₛ | 0.8896 / 2.272 / 0.4061 |
| Mesh / step effective length | 1,540 m / 1,155 m |
| Touch / step voltage limits | 840.5 V / 2,696 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.