Worked example · IEEE 80-2013

IEEE 80 Annex B square grid

Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.

The first Annex B design uses a 70 × 70 m grid with 7 m pitch, 0.5 m burial and no rods. The maximum grid current is based on the 3.18 kA bus fault and a 0.6 split.

Mesh or step limit exceeded

Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.

Sverak resistance
2.7757 Ω
Ground potential rise
5,296 V
Corner mesh voltage
1,001.6 V
Corner step voltage
609.73 V

Inputs

Grid geometry
m
m
m
m
mm
m
Fault current
kA
×
×
Use the IEEE 80 RMS decrement factor for the applicable X/R and fault duration.
Exposure limits
Ω·m
mm
Enter 0 for bare earth.
Ω·m
s

Ground grid plan & potential profile

Live schematic
Grid Rg2.776 ΩGPR5,296 VMesh volts1,002 VStep volts609.7 VCOPPER MESH · PLAN70 m × 70 mPOTENTIAL RISE · SECTIONGPR 5,296 VMesh 1,002 VGrid edgeRemote earthMesh / touch limit119.2%Step / limit22.62%
The schematic potential profile distinguishes GPR from the local mesh and step voltage.

Derived values & comparisons
Laurent–Niemann estimate2.7918 Ω
Circular plate reference2.5321 Ω
Maximum earth current Iɢ1.908 kA
Grid area4,900 m²
Horizontal / total buried length1,540 m / 1,540 m
Mesh bay count10 × 10
Fitted pitches7 m × 7 m
Kₘ / Kᵢ / Kₛ0.8896 / 2.272 / 0.4061
Mesh / step effective length1,540 m / 1,155 m
Touch / step voltage limits840.5 V / 2,696 V

Screening scope. Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.

Try this. Compare ground resistance with 2.78 Ω and mesh voltage with the published rounded result of roughly 1,002 V.

Calculation method

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.

Standards and model assumptions