Worked example · IEEE 80-2013

High-resistivity ridge switchyard

Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.

An exposed ridge has high apparent native resistivity and limited area. The uniform-soil estimate is a starting point for evaluating the site survey.

Mesh or step limit exceeded

Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.

Sverak resistance
7.9611 Ω
Ground potential rise
24,576 V
Corner mesh voltage
5,455.6 V
Corner step voltage
2,967.4 V

Inputs

Grid geometry
m
m
m
m
mm
m
m
Fault current
kA
×
×
Use the IEEE 80 RMS decrement factor for the applicable X/R and fault duration.
Exposure limits
Ω·m
mm
Enter 0 for bare earth.
Ω·m
s

Ground grid plan & potential profile

Live schematic
Grid Rg7.961 ΩGPR24,580 VMesh volts5,456 VStep volts2,967 VCOPPER MESH · PLAN50 m × 40 mPOTENTIAL RISE · SECTIONGPR 24,580 VMesh 5,456 VGrid edgeRemote earthMesh / touch limit523.2%Step / limit80.66%
The schematic potential profile distinguishes GPR from the local mesh and step voltage.

Derived values & comparisons
Laurent–Niemann estimate8.0606 Ω
Circular plate reference6.7377 Ω
Maximum earth current Iɢ3.087 kA
Grid area2,000 m²
Horizontal / total buried length490 m / 514 m
Mesh bay count5 × 4
Fitted pitches10 m × 10 m
Kₘ / Kᵢ / Kₛ0.9459 / 1.452 / 0.3776
Mesh / step effective length528.6 m / 387.9 m
Touch / step voltage limits1,043 V / 3,679 V

Screening scope. Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.

Try this. Compare the Laurent and Sverak estimates, then evaluate a denser proposed mesh.

Calculation method

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.

Standards and model assumptions