GroundGridLab · IEEE 80-2013
Perimeter rod retrofit
A regular grid in medium-resistivity soil is extended with equal-length rods on its boundary. The yard remains limited by the existing property line.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 1.9857 Ω
- Ground potential rise
- 7,372.4 V
- Corner mesh voltage
- 1,004.6 V
- Corner step voltage
- 821.19 V
Inputs
| Grid length | 60 m |
|---|---|
| Grid width | 48 m |
| Maximum mesh pitch | 6 m |
| Burial depth | 0.5 m |
| Conductor diameter | 12 mm |
| Total rod length | 96 m |
| Rod placement | Corners / perimeter |
| Individual rod length | 4 m |
| Symmetrical ground fault | 6.8 kA |
| Current split factor | 0.52 × |
| Decrement factor | 1.05 × |
| Native soil resistivity | 220 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 2,700 Ω·m |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 2.0055 Ω |
|---|---|
| Circular plate reference | 1.8165 Ω |
| Maximum earth current Iɢ | 3.7128 kA |
| Grid area | 2,880 m² |
| Horizontal / total buried length | 1,068 m / 1,164 m |
| Mesh bay count | 10 × 8 |
| Fitted pitches | 6 m × 6 m |
| Kₘ / Kᵢ / Kₛ | 0.7121 / 2.112 / 0.4201 |
| Mesh / step effective length | 1,223 m / 882.6 m |
| Touch / step voltage limits | 639.1 V / 2,064 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.