Worked example · IEEE 80-2013

Rectangular switchyard with rods

Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.

An 80 × 60 m yard uses a copper mat with 72 m of vertical electrode length at the perimeter. Some fault current returns through metallic connections.

Mesh or step limit exceeded

Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.

Sverak resistance
1.0811 Ω
Ground potential rise
5,448.7 V
Corner mesh voltage
1,009.1 V
Corner step voltage
587.56 V

Inputs

Grid geometry
m
m
m
m
mm
m
m
Fault current
kA
×
×
Use the IEEE 80 RMS decrement factor for the applicable X/R and fault duration.
Exposure limits
Ω·m
mm
Enter 0 for bare earth.
Ω·m
s

Ground grid plan & potential profile

Live schematic
Grid Rg1.081 ΩGPR5,449 VMesh volts1,009 VStep volts587.6 VCOPPER MESH · PLAN80 m × 60 mPOTENTIAL RISE · SECTIONGPR 5,449 VMesh 1,009 VGrid edgeRemote earthMesh / touch limit168.2%Step / limit30.81%
The schematic potential profile distinguishes GPR from the local mesh and step voltage.

Derived values & comparisons
Laurent–Niemann estimate1.0874 Ω
Circular plate reference0.95937 Ω
Maximum earth current Iɢ5.04 kA
Grid area4,800 m²
Horizontal / total buried length1,100 m / 1,172 m
Mesh bay count8 × 6
Fitted pitches10 m × 10 m
Kₘ / Kᵢ / Kₛ0.894 / 1.813 / 0.3799
Mesh / step effective length1,214 m / 886.2 m
Touch / step voltage limits599.8 V / 1,907 V

Screening scope. Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.

Try this. Keep fault current constant and reduce the split factor to see GPR and the two exposure voltages scale together.

Calculation method

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.

Standards and model assumptions