GroundGridLab · IEEE 80-2013
Unequal mesh pitches
A narrow extension creates different bay dimensions in the two directions. Use the screen to identify the geometry that needs a more detailed study.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 3.1124 Ω
- Ground potential rise
- 7,235.4 V
- Corner mesh voltage
- 1,663.3 V
- Corner step voltage
- 868.28 V
Inputs
| Grid length | 43 m |
|---|---|
| Grid width | 12 m |
| Maximum mesh pitch | 8 m |
| Burial depth | 0.55 m |
| Conductor diameter | 12 mm |
| Total rod length | 18 m |
| Rod placement | Interior only |
| Symmetrical ground fault | 5.4 kA |
| Current split factor | 0.41 × |
| Decrement factor | 1.05 × |
| Native soil resistivity | 135 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 2,500 Ω·m |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 3.2179 Ω |
|---|---|
| Circular plate reference | 2.6334 Ω |
| Maximum earth current Iɢ | 2.3247 kA |
| Grid area | 516 m² |
| Horizontal / total buried length | 213 m / 231 m |
| Mesh bay count | 6 × 2 |
| Fitted pitches | 7.167 m × 6 m |
| Kₘ / Kᵢ / Kₛ | 0.9605 / 1.275 / 0.38 |
| Mesh / step effective length | 231 m / 175.1 m |
| Touch / step voltage limits | 598.6 V / 1,902 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.