Worked example · IEEE 80-2013

Compact service-yard mat

Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.

A small service-yard mat has little horizontal length compared with the perimeter of a large yard. Estimate the screened corner exposure using the smaller geometry.

Mesh or step limit exceeded

Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.

Sverak resistance
2.9975 Ω
Ground potential rise
4,532.2 V
Corner mesh voltage
760.36 V
Corner step voltage
734.62 V

Inputs

Grid geometry
m
m
m
m
mm
m
m
Fault current
kA
×
×
Use the IEEE 80 RMS decrement factor for the applicable X/R and fault duration.
Exposure limits
Ω·m
mm
Enter 0 for bare earth.
s

Ground grid plan & potential profile

Live schematic
Grid Rg2.998 ΩGPR4,532 VMesh volts760.4 VStep volts734.6 VCOPPER MESH · PLAN20 m × 12 mPOTENTIAL RISE · SECTIONGPR 4,532 VMesh 760.4 VGrid edgeRemote earthMesh / touch limit408.4%Step / limit290.8%
The schematic potential profile distinguishes GPR from the local mesh and step voltage.

Derived values & comparisons
Laurent–Niemann estimate3.123 Ω
Circular plate reference2.5743 Ω
Maximum earth current Iɢ1.512 kA
Grid area240 m²
Horizontal / total buried length152 m / 164 m
Mesh bay count5 × 3
Fitted pitches4 m × 4 m
Kₘ / Kᵢ / Kₛ0.7095 / 1.358 / 0.4936
Mesh / step effective length172.5 m / 124.2 m
Touch / step voltage limits186.2 V / 252.6 V

Screening scope. Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.

Try this. Check what happens to the fitted pitch and total copper length when you reduce the pitch from 4 m to 3 m.

Calculation method

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.