Compact service-yard mat
A small service-yard mat has little horizontal length compared with the perimeter of a large yard. Estimate the screened corner exposure using the smaller geometry.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 2.9975 Ω
- Ground potential rise
- 4,532.2 V
- Corner mesh voltage
- 760.36 V
- Corner step voltage
- 734.62 V
Inputs
| Grid length | 20 m |
|---|---|
| Grid width | 12 m |
| Maximum mesh pitch | 4 m |
| Burial depth | 0.45 m |
| Conductor diameter | 12 mm |
| Total rod length | 12 m |
| Rod placement | Corners / perimeter |
| Individual rod length | 3 m |
| Symmetrical ground fault | 4.5 kA |
| Current split factor | 0.32 × |
| Decrement factor | 1.05 × |
| Native soil resistivity | 90 Ω·m |
| Surface layer thickness | 0 mm |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 3.123 Ω |
|---|---|
| Circular plate reference | 2.5743 Ω |
| Maximum earth current Iɢ | 1.512 kA |
| Grid area | 240 m² |
| Horizontal / total buried length | 152 m / 164 m |
| Mesh bay count | 5 × 3 |
| Fitted pitches | 4 m × 4 m |
| Kₘ / Kᵢ / Kₛ | 0.7095 / 1.358 / 0.4936 |
| Mesh / step effective length | 172.5 m / 124.2 m |
| Touch / step voltage limits | 186.2 V / 252.6 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.