GroundGridLab · IEEE 80-2013
Generator step-up transformer yard
A 96 × 64 m transformer yard has local contribution to the symmetrical fault and a separate grid-current split estimate.
Mesh & step limits met. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 0.58642 Ω
- Ground potential rise
- 3,800 V
- Corner mesh voltage
- 558.26 V
- Corner step voltage
- 349.27 V
Inputs
| Grid length | 96 m |
|---|---|
| Grid width | 64 m |
| Maximum mesh pitch | 8 m |
| Burial depth | 0.6 m |
| Conductor diameter | 14 mm |
| Total rod length | 84 m |
| Rod placement | Corners / perimeter |
| Individual rod length | 6 m |
| Symmetrical ground fault | 12 kA |
| Current split factor | 0.45 × |
| Decrement factor | 1.2 × |
| Native soil resistivity | 95 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 2,500 Ω·m |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 0.59042 Ω |
|---|---|
| Circular plate reference | 0.53705 Ω |
| Maximum earth current Iɢ | 6.48 kA |
| Grid area | 6,144 m² |
| Horizontal / total buried length | 1,696 m / 1,780 m |
| Mesh bay count | 12 × 8 |
| Fitted pitches | 8 m × 8 m |
| Kₘ / Kᵢ / Kₛ | 0.7452 / 2.229 / 0.342 |
| Mesh / step effective length | 1,832 m / 1,343 m |
| Touch / step voltage limits | 595.6 V / 1,890 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.