Worked example · IEEE 80-2013

Generator step-up transformer yard

Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.

A 96 × 64 m transformer yard has local contribution to the symmetrical fault and a separate grid-current split estimate.

Mesh & step limits met

Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.

Sverak resistance
0.58642 Ω
Ground potential rise
3,800 V
Corner mesh voltage
558.26 V
Corner step voltage
349.27 V

Inputs

Grid geometry
m
m
m
m
mm
m
m
Fault current
kA
×
×
Use the IEEE 80 RMS decrement factor for the applicable X/R and fault duration.
Exposure limits
Ω·m
mm
Enter 0 for bare earth.
Ω·m
s

Ground grid plan & potential profile

Live schematic
Grid Rg0.5864 ΩGPR3,800 VMesh volts558.3 VStep volts349.3 VCOPPER MESH · PLAN96 m × 64 mPOTENTIAL RISE · SECTIONGPR 3,800 VMesh 558.3 VGrid edgeRemote earthMesh / touch limit93.74%Step / limit18.48%
The schematic potential profile distinguishes GPR from the local mesh and step voltage.

Derived values & comparisons
Laurent–Niemann estimate0.59042 Ω
Circular plate reference0.53705 Ω
Maximum earth current Iɢ6.48 kA
Grid area6,144 m²
Horizontal / total buried length1,696 m / 1,780 m
Mesh bay count12 × 8
Fitted pitches8 m × 8 m
Kₘ / Kᵢ / Kₛ0.7452 / 2.229 / 0.342
Mesh / step effective length1,832 m / 1,343 m
Touch / step voltage limits595.6 V / 1,890 V

Screening scope. Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.

Try this. Change the decrement factor without changing the current split to isolate DC offset sensitivity.

Calculation method

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.

Standards and model assumptions