GroundGridLab · IEEE 80-2013
High-resistivity ridge switchyard
An exposed ridge has high apparent native resistivity and limited area. The uniform-soil estimate is a starting point for evaluating the site survey.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 7.9611 Ω
- Ground potential rise
- 24,576 V
- Corner mesh voltage
- 5,455.6 V
- Corner step voltage
- 2,967.4 V
Inputs
| Grid length | 50 m |
|---|---|
| Grid width | 40 m |
| Maximum mesh pitch | 10 m |
| Burial depth | 0.5 m |
| Conductor diameter | 12 mm |
| Total rod length | 24 m |
| Rod placement | Corners / perimeter |
| Individual rod length | 3 m |
| Symmetrical ground fault | 4.2 kA |
| Current split factor | 0.7 × |
| Decrement factor | 1.05 × |
| Native soil resistivity | 680 Ω·m |
| Surface layer thickness | 140 mm |
| Surface material resistivity | 4,500 Ω·m |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 8.0606 Ω |
|---|---|
| Circular plate reference | 6.7377 Ω |
| Maximum earth current Iɢ | 3.087 kA |
| Grid area | 2,000 m² |
| Horizontal / total buried length | 490 m / 514 m |
| Mesh bay count | 5 × 4 |
| Fitted pitches | 10 m × 10 m |
| Kₘ / Kᵢ / Kₛ | 0.9459 / 1.452 / 0.3776 |
| Mesh / step effective length | 528.6 m / 387.9 m |
| Touch / step voltage limits | 1,043 V / 3,679 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.