Wide baffle spacing on an existing exchanger
An existing shell uses a spacing larger than the internal diameter.
Segmental baffle cutaway
Aₛ = DₛB(p − Dₒ)/p · Nu = 0.36 Re⁰·⁵⁵ Pr¹ᐟ³ (μ/μwall)⁰·¹⁴
- Crossflow area
- 0.0522m²
- Shell velocity
- 0.32567m/s
- Shell hₒ
- 2,645.4W/(m²·K)
- Shell ΔP
- 3.5299kPa
- Baffle spacing falls outside the preliminary spacing window.
- Gross baffle window is smaller than the bundle crossflow area. Check window velocity and leakage separately.
Inputs
Calculated results
- Bundle crossflow area
- 0.0522 m²
- Crossflow velocity
- 0.32567 m/s
- Shell-side film hₒ
- 2,645.4 W/(m²·K)
- Shell-side pressure drop
- 3.5299 kPa
- Equivalent diameter
- 18.849 mm
- Shell Reynolds number
- 6,150.8
- Gross baffle window
- 0.031093 m²
- Estimated segmental baffles
- 7
- Crossflow sections
- 8
- Shell mass flux
- 326.32 kg/(m²·s)
- Prandtl number
- 6.7419
- Kern friction factor
- 0.33904
- Baffle spacing / shell ID
- 1.2889
- Screening minimum spacing
- 0.09 m
Worked solution
Preset calculation · Metric SI
- From the shell bore, spacing, and clear pitch, find 0.0522 m² available for crossflow.
- Use the pitch cell to obtain a hydraulic equivalent diameter of 18.849 mm and Reynolds number of 6,150.8.
- Apply the Kern screen across 8 sections to estimate 2,645.4 W/(m²·K) for hₒ and 3.5299 kPa for pressure loss.
Check the upper spacing limit and compute the approximate number of crossflow sections. Mechanical support and vibration need their own check.
Calculation basis
Kern crossflow area uses the notional tube row at the shell equator. Equivalent diameter comes from the open area and wetted perimeter of a square or triangular pitch cell.
The 25% nominal baffle-cut correlation estimates shell-side hₒ and pressure drop. The entered cut changes the gross segment window and diagram. Leakage, bypass, window obstructions, and nozzle losses require a more detailed method.
The spacing screen runs from the larger of 0.2Dₛ and 50 mm to Dₛ. Maximum unsupported length and vibration depend on the actual tube material and layout.
Methodology and references