Heat exchanger LMTD, correction factor & area
Size heat transfer surface from terminal temperatures and service U. Check Fₜ for 1–2 and 2–4 shell-and-tube layouts.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 21.059m²
- LMTD
- 75K
- Fₜ factor
- 0.92094
- Rated duty
- 1,709.5kW
- Within the displayed screening checks.
Inputs
Calculated results
- Required surface
- 21.059 m²
- Log mean ΔT
- 75 K
- Correction factor Fₜ
- 0.92094
- Available duty
- 1,709.5 kW
- Target duty
- 800 kW
- Corrected mean ΔT
- 69.07 K
- Terminal difference A
- 75 K
- Terminal difference B
- 75 K
- Cold temperature ratio P
- 0.4
- Stream temperature ratio R
- 1
- Duty reserve vs. target
- 113.69 %
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.
Methodology and references