Re-rating a fixed exchanger surface
An existing oil service exchanger has a known 118 m² of outside surface and a revised service U.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 125.33m²
- LMTD
- 62.274K
- Fₜ factor
- 1
- Rated duty
- 3,012.8kW
- Available surface falls short of the target duty.
Inputs
Calculated results
- Required surface
- 125.33 m²
- Log mean ΔT
- 62.274 K
- Correction factor Fₜ
- 1
- Available duty
- 3,012.8 kW
- Target duty
- 3,200 kW
- Corrected mean ΔT
- 62.274 K
- Terminal difference A
- 69 K
- Terminal difference B
- 56 K
- Cold temperature ratio P
- 0.39474
- Stream temperature ratio R
- 1.2889
- Duty reserve vs. target
- -5.8495 %
Worked solution
Preset calculation · Metric SI
- Pair the terminal temperatures to obtain 69 K and 56 K. Their log mean is 62.274 K.
- Use P = 0.39474 and R = 1.2889 for the shell correction where applicable. Fₜ = 1.
- Divide 3,200 kW by 410 W/(m²·K) times the corrected drive of 62.274 K to obtain 125.33 m².
Compare available duty with the 3.2 MW target. Adjust service U to see the coefficient needed at fixed surface.
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.