Parallel-flow wash-water heater
A compact co-current heater uses hot condensate to preheat a wash-water loop. The narrow gap is at the common outlet.
Terminal temperature profile
Q = U × A × Fₜ × ΔTₗₘ
- Area needed
- 16.938m²
- LMTD
- 33.34K
- Fₜ factor
- 1
- Rated duty
- 566.79kW
- Within the displayed screening checks.
Inputs
Calculated results
- Required surface
- 16.938 m²
- Log mean ΔT
- 33.34 K
- Correction factor Fₜ
- 1
- Available duty
- 566.79 kW
- Target duty
- 480 kW
- Corrected mean ΔT
- 33.34 K
- Terminal difference A
- 75 K
- Terminal difference B
- 11 K
- Cold temperature ratio P
- 0.41333
- Stream temperature ratio R
- 1.0645
- Duty reserve vs. target
- 18.081 %
Worked solution
Preset calculation · Metric SI
- Pair the terminal temperatures to obtain 75 K and 11 K. Their log mean is 33.34 K.
- Use P = 0.41333 and R = 1.0645 for the shell correction where applicable. Fₜ = 1.
- Divide 480 kW by 850 W/(m²·K) times the corrected drive of 33.34 K to obtain 16.938 m².
Compare the outlet gap with the logarithmic mean. Switching to counterflow holds the temperatures fixed while changing the terminal pairing.
Calculation basis
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.
Methodology and references