Heat exchanger LMTD, correction factor & area

Size heat transfer surface from terminal temperatures and service U. Check Fₜ for 1–2 and 2–4 shell-and-tube layouts.

Terminal temperature profile

Q = U × A × Fₜ × ΔTₗₘ

Edit inputs ↓
Area needed
21.059m²
LMTD
75K
Fₜ factor
0.92094
Rated duty
1,709.5kW
Terminal temperature profile150 °C100 °C75 °C25 °CHOT STREAM →← COLD STREAMEnd AEnd BFₜ 00.75 screenFₜ 1
The lines join terminal temperatures along the hot-stream direction. Shell cases use a counterflow reference for the temperature plot.
  • Within the displayed screening checks.

Inputs

°C
°C
°C
°C
kW
W/(m²·K)
m²

Calculated results

Required surface
21.059 m²
Log mean ΔT
75 K
Correction factor Fₜ
0.92094
Available duty
1,709.5 kW
Target duty
800 kW
Corrected mean ΔT
69.07 K
Terminal difference A
75 K
Terminal difference B
75 K
Cold temperature ratio P
0.4
Stream temperature ratio R
1
Duty reserve vs. target
113.69 %

Calculation basis

Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.

The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.

For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.