Parallel-flow wash-water heater

A compact co-current heater uses hot condensate to preheat a wash-water loop. The narrow gap is at the common outlet.

Terminal temperature profile

Q = U × A × Fₜ × ΔTₗₘ

Edit inputs ↓
Area needed
16.938m²
LMTD
33.34K
Fₜ factor
1
Rated duty
566.79kW
Terminal temperature profile95 °C62 °C20 °C51 °CHOT STREAM →COLD STREAM →End AEnd BFₜ 00.75 screenFₜ 1
The lines join terminal temperatures along the hot-stream direction. Shell cases use a counterflow reference for the temperature plot.
  • Within the displayed screening checks.

Inputs

°C
°C
°C
°C
kW
W/(m²·K)
m²

Calculated results

Required surface
16.938 m²
Log mean ΔT
33.34 K
Correction factor Fₜ
1
Available duty
566.79 kW
Target duty
480 kW
Corrected mean ΔT
33.34 K
Terminal difference A
75 K
Terminal difference B
11 K
Cold temperature ratio P
0.41333
Stream temperature ratio R
1.0645
Duty reserve vs. target
18.081 %

Worked solution

Preset calculation · Metric SI

  1. Pair the terminal temperatures to obtain 75 K and 11 K. Their log mean is 33.34 K.
  2. Use P = 0.41333 and R = 1.0645 for the shell correction where applicable. Fₜ = 1.
  3. Divide 480 kW by 850 W/(m²·K) times the corrected drive of 33.34 K to obtain 16.938 m².

Compare the outlet gap with the logarithmic mean. Switching to counterflow holds the temperatures fixed while changing the terminal pairing.

Calculation basis

Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.

The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.

For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.

Methodology and references