Flat titanium plate resistance
A thin corrosion-resistant plate separates two clean liquid streams with relatively high film coefficients.
Thermal resistance stack
U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k
- Clean U
- 1,932W/(m²·K)
- Service U
- 1,486.8W/(m²·K)
- Cleanliness
- 76.955%
- Largest term
- Outside film
- Service U is below 80% of clean U. Review the fouling allowance and cleaning basis.
Inputs
Calculated results
- Clean overall U
- 1,932 W/(m²·K)
- Fouled service U
- 1,486.8 W/(m²·K)
- Cleanliness
- 76.955 %
- Controlling resistance
- Outside film
- Total fouled resistance
- 0.00067261 m²·K/W
- Inside film resistance
- 0.00022222 m²·K/W
- Inside fouling resistance
- 6.50e-5 m²·K/W
- Wall resistance
- 2.51e-5 m²·K/W
- Outside fouling resistance
- 9.00e-5 m²·K/W
- Outside film resistance
- 0.00027027 m²·K/W
- Fouling loss in U
- 23.045 %
Worked solution
Preset calculation · Metric SI
- Put both films, both fouling terms, and the wall on one surface basis. The wall contributes 2.51e-5 m²·K/W.
- Sum the resistances to get 0.00067261 m²·K/W. Its reciprocal gives service U of 1,486.8 W/(m²·K).
- Omit the fouling terms to get clean U of 1,932 W/(m²·K), then divide service U by clean U for 76.955 % cleanliness.
Wall resistance is t/k on the same area basis as both films. Vary plate thickness to see how little it contributes here.
Calculation basis
For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.
For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.
Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.
Methodology and references