HeatExchangerLab

Seawater-side fouling allowance

A seawater-cooled exchanger uses an elevated inside fouling allowance on the local tube surface.

Thermal resistance stack

U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k

Edit inputs ↓
Clean U
756.36W/(m²·K)
Service U
452.41W/(m²·K)
Cleanliness
59.814%
Largest term
Inside fouling
Thermal resistance stackRESISTANCE TERMSHARE OF TOTALInside film23.329 %Inside fouling36.114 %Metal wall1.14 %Outside fouling4.0717 %Outside film35.345 %0% clean80% screen100% clean
Each segment adds resistance on the same surface-area basis. The longest segment makes the largest contribution.
  • Service U is below 80% of clean U. Review the fouling allowance and cleaning basis.

Inputs

W/(m²·K)
W/(m²·K)
m²·K/W
m²·K/W
mm
mm
W/(m·K)

Calculated results

Clean overall U
756.36 W/(m²·K)
Fouled service U
452.41 W/(m²·K)
Cleanliness
59.814 %
Controlling resistance
Inside fouling
Total fouled resistance
0.0022104 m²·K/W
Inside film resistance
0.00051567 m²·K/W
Inside fouling resistance
0.00079825 m²·K/W
Wall resistance
2.52e-5 m²·K/W
Outside fouling resistance
9.00e-5 m²·K/W
Outside film resistance
0.00078125 m²·K/W
Fouling loss in U
40.186 %

Worked solution

Preset calculation · Metric SI

  1. Put both films, both fouling terms, and the wall on one surface basis. The wall contributes 2.52e-5 m²·K/W.
  2. Sum the resistances to get 0.0022104 m²·K/W. Its reciprocal gives service U of 452.41 W/(m²·K).
  3. Omit the fouling terms to get clean U of 756.36 W/(m²·K), then divide service U by clean U for 59.814 % cleanliness.

Follow inside fouling after the outside-area correction. Compare the cleanliness result against the 80% screen.

Calculation basis

For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.

For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.

Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.

Methodology and references