Overall heat transfer coefficient & fouling
Compare clean and fouled U, account for cylindrical or flat walls, and see what controls thermal resistance.
Thermal resistance stack
U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k
- Clean U
- 621.06W/(m²·K)
- Service U
- 461.46W/(m²·K)
- Cleanliness
- 74.302%
- Largest term
- Outside film
- Service U is below 80% of clean U. Review the fouling allowance and cleaning basis.
Inputs
Calculated results
- Clean overall U
- 621.06 W/(m²·K)
- Fouled service U
- 461.46 W/(m²·K)
- Cleanliness
- 74.302 %
- Controlling resistance
- Outside film
- Total fouled resistance
- 0.002167 m²·K/W
- Inside film resistance
- 0.0005473 m²·K/W
- Inside fouling resistance
- 0.00020688 m²·K/W
- Wall resistance
- 0.00011047 m²·K/W
- Outside fouling resistance
- 0.00035 m²·K/W
- Outside film resistance
- 0.00095238 m²·K/W
- Fouling loss in U
- 25.698 %
Calculation basis
For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.
For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.
Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.