HeatExchangerLab

Overall heat transfer coefficient & fouling

Compare clean and fouled U, account for cylindrical or flat walls, and see what controls thermal resistance.

Thermal resistance stack

U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k

Edit inputs ↓
Clean U
621.06W/(m²·K)
Service U
461.46W/(m²·K)
Cleanliness
74.302%
Largest term
Outside film
Thermal resistance stackRESISTANCE TERMSHARE OF TOTALInside film25.256 %Inside fouling9.5466 %Metal wall5.0977 %Outside fouling16.151 %Outside film43.949 %0% clean80% screen100% clean
Each segment adds resistance on the same surface-area basis. The longest segment makes the largest contribution.
  • Service U is below 80% of clean U. Review the fouling allowance and cleaning basis.

Inputs

W/(m²·K)
W/(m²·K)
m²·K/W
m²·K/W
mm
mm
W/(m·K)

Calculated results

Clean overall U
621.06 W/(m²·K)
Fouled service U
461.46 W/(m²·K)
Cleanliness
74.302 %
Controlling resistance
Outside film
Total fouled resistance
0.002167 m²·K/W
Inside film resistance
0.0005473 m²·K/W
Inside fouling resistance
0.00020688 m²·K/W
Wall resistance
0.00011047 m²·K/W
Outside fouling resistance
0.00035 m²·K/W
Outside film resistance
0.00095238 m²·K/W
Fouling loss in U
25.698 %

Calculation basis

For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.

For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.

Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.

Methodology and references