HeatExchangerLab

Thick alloy tube wall penalty

A thick corrosion-resistant alloy tube trades thermal conductance for service compatibility.

Thermal resistance stack

U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k

Edit inputs ↓
Clean U
1,004W/(m²·K)
Service U
881.54W/(m²·K)
Cleanliness
87.8%
Largest term
Metal wall
Thermal resistance stackRESISTANCE TERMSHARE OF TOTALInside film22.979 %Inside fouling5.1474 %Metal wall40.334 %Outside fouling7.0523 %Outside film24.487 %0% clean80% screen100% clean
Each segment adds resistance on the same surface-area basis. The longest segment makes the largest contribution.
  • Within the displayed screening checks.

Inputs

W/(m²·K)
W/(m²·K)
m²·K/W
m²·K/W
mm
mm
W/(m·K)

Calculated results

Clean overall U
1,004 W/(m²·K)
Fouled service U
881.54 W/(m²·K)
Cleanliness
87.8 %
Controlling resistance
Metal wall
Total fouled resistance
0.0011344 m²·K/W
Inside film resistance
0.00026067 m²·K/W
Inside fouling resistance
5.84e-5 m²·K/W
Wall resistance
0.00045754 m²·K/W
Outside fouling resistance
8.00e-5 m²·K/W
Outside film resistance
0.00027778 m²·K/W
Fouling loss in U
12.2 %

Worked solution

Preset calculation · Metric SI

  1. Put both films, both fouling terms, and the wall on one surface basis. The wall contributes 0.00045754 m²·K/W.
  2. Sum the resistances to get 0.0011344 m²·K/W. Its reciprocal gives service U of 881.54 W/(m²·K).
  3. Omit the fouling terms to get clean U of 1,004 W/(m²·K), then divide service U by clean U for 87.8 % cleanliness.

Compare the metal wall with the film contributions. Increasing thickness also increases the inside-to-outside area ratio.

Calculation basis

For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.

For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.

Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.

Methodology and references