HeatExchangerLab

Tube bundle constrained by an existing shell

A retrofit must fit an existing shell even though the updated duty requires considerably more surface.

Tube bundle and pass routing

ΔP = [f × (L/Dᵢ) × nₚ + 4(nₚ − 1)] × ρv²/2

Edit inputs ↓
Required tubes
472
Tube velocity
0.50822m/s
Tube ΔP
1.9515kPa
Reynolds
13.63K
Tube bundle and pass routing90° tube pitch2 passes · 236 tubes/pass0Liquid velocity3.6 m/s
The section shows a sample of the selected pitch lattice. The routing shows the selected number of tube passes.
  • The required tube count exceeds the estimated centered bundle capacity.
  • Tube velocity is below the 0.9 m/s fouling screen.

Inputs

m
m²
m
mm
L/min
kg/m³
mPa·s
mm

Calculated results

Required tubes
472
Tube velocity
0.50822 m/s
Tube-side pressure drop
1.9515 kPa
Tube Reynolds number
13,627
Estimated tubes that fit
144
Tubes per pass
236
Installed outside area
158.19 m²
Tube inside diameter
22.098 mm
Tube center pitch
35.56 mm
Straight tube loss
1.4375 kPa
Return pass loss
0.51399 kPa
Darcy friction factor
0.02943

Worked solution

Preset calculation · Metric SI

  1. Divide the required area by the area per tube and round up to a complete pass grouping. The result is 472 tubes.
  2. Put the flow through 236 tubes per pass. The resulting tube speed and Reynolds number are 0.50822 m/s and 13,627.
  3. Add 1.4375 kPa of straight loss and 0.51399 kPa of return loss.

Compare the required count with the centered-lattice estimate. Increase tube length or shell ID to explore how the fit changes.

Calculation basis

Required outside area divided by πDₒL gives the raw tube count. Round up to fill complete passes. Bundle capacity counts centers on the selected pitch lattice inside a circular limit after bundle clearance.

The bundle screen uses a centered lattice and omits pass-partition lanes, tie rods, and detailed tubesheet constraints. Confirm actual tube count with a layout drawing.

Straight loss uses Darcy–Weisbach with 64/Re for laminar flow and Haaland for turbulent flow. Add K = 4 per return pass. The default 0.9–2.4 m/s screening band is for initial liquid-service review.

Methodology and references