Emergency Egress Lighting
Screen NFPA 101 floor illuminance and uniformity at startup and 90 minutes, then estimate inverter VA and battery Ah.
Inputs
View results ↑- Initial avg.
- 1.35fc
- 90-min avg.
- 0.92fc
- Worst max:min
- 17.2:1
- Battery bank
- 8.52Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Within screen- Initial mean1.35 / ≥ 1 fc within screen
- Initial minimum0.18 / ≥ 0.1 fc within screen
- 90-minute mean0.918 / ≥ 0.6 fc within screen
- 90-minute minimum0.122 / ≥ 0.06 fc within screen
- Initial max / min17.222 / ≤ 40 :1 within screen
- 90-minute max / min17.222 / ≤ 40 :1 within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 576ft² |
|---|---|
| Total initial fixture output | 9,120lm |
| Emitted flux per floor area | 15.83lm/ft² |
| Initial minimum | 0.18fc |
| Initial maximum | 3.1fc |
| Initial max / min | 17.22:1 |
| 90-minute minimum | 0.12fc |
| 90-minute maximum | 2.11fc |
| 90-minute max / min | 17.22:1 |
| Inverter real load | 96W |
| Inverter apparent load | 120VA |
| Assumed fixture power factor | 0.8 |
| Estimated DC current | 4.55A |
| DC energy before derating | 163.64Wh |
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Emergency Egress Lighting
Inputs
| Egress path length | 96ft |
|---|---|
| Path clear width | 6ft |
| Initial average | 1.35fc |
| Initial minimum | 0.18fc |
| Initial maximum | 3.1fc |
| 90-minute readings | Apply output retention factor |
| End-of-discharge retention | 0.68 |
| Emergency fixtures | 8 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 12W |
| Apparent input per fixture | 15VA |
| Battery system voltage | 24 V DC |
| Inverter efficiency | 0.88 |
| Battery aging / temperature factor | 1.25× |
Results
| Initial avg. | 1.35fc |
|---|---|
| 90-min avg. | 0.92fc |
| Worst max:min | 17.2:1 |
| Battery bank | 8.52Ah |
| Walking surface area | 576ft² |
| Total initial fixture output | 9,120lm |
| Emitted flux per floor area | 15.83lm/ft² |
| Initial minimum | 0.18fc |
| Initial maximum | 3.1fc |
| Initial max / min | 17.22:1 |
| 90-minute minimum | 0.12fc |
| 90-minute maximum | 2.11fc |
| 90-minute max / min | 17.22:1 |
| Inverter real load | 96W |
| Inverter apparent load | 120VA |
| Assumed fixture power factor | 0.8 |
| Estimated DC current | 4.55A |
| DC energy before derating | 163.64Wh |
NFPA 101 egress screen
- Initial mean · 1.35 / ≥ 1 fc · Within screen
- Initial minimum · 0.18 / ≥ 0.1 fc · Within screen
- 90-minute mean · 0.918 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.122 / ≥ 0.06 fc · Within screen
- Initial max / min · 17.222 / ≤ 40 :1 · Within screen
- 90-minute max / min · 17.222 / ≤ 40 :1 · Within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.