Stairwell with a 90-minute survey
Enter measurements at both time points, using readings from the same walking path. The survey catches a larger uniformity ratio at the end.
Inputs
View results ↑- Initial avg.
- 1.25fc
- 90-min avg.
- 0.71fc
- Worst max:min
- 42.5:1
- Battery bank
- 8.88Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Review needed- Initial mean1.25 / ≥ 1 fc within screen
- Initial minimum0.15 / ≥ 0.1 fc within screen
- 90-minute mean0.71 / ≥ 0.6 fc within screen
- 90-minute minimum0.08 / ≥ 0.06 fc within screen
- Initial max / min18.667 / ≤ 40 :1 within screen
- 90-minute max / min42.5 / ≤ 40 :1 outside screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 190ft² |
|---|---|
| Total initial fixture output | 4,750lm |
| Emitted flux per floor area | 25lm/ft² |
| Initial minimum | 0.15fc |
| Initial maximum | 2.8fc |
| Initial max / min | 18.67:1 |
| 90-minute minimum | 0.08fc |
| 90-minute maximum | 3.4fc |
| 90-minute max / min | 42.5:1 |
| Inverter real load | 50W |
| Inverter apparent load | 65VA |
| Assumed fixture power factor | 0.769 |
| Estimated DC current | 4.73A |
| DC energy before derating | 85.23Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1.25 fc and 0.15 fc. The corresponding 90-minute values are 0.71 fc and 0.08 fc.
- The worst maximum-to-minimum ratio is 42.5:1 against the 40:1 limit.
- The inverter supplies 65 VA and 50 W. For 90 minutes, the estimated derated bank is 8.88 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Stairwell with a 90-minute survey
Inputs
| Egress path length | 38ft |
|---|---|
| Path clear width | 5ft |
| Initial average | 1.25fc |
| Initial minimum | 0.15fc |
| Initial maximum | 2.8fc |
| 90-minute readings | Enter measured or modeled readings |
| 90-minute average | 0.71fc |
| 90-minute minimum | 0.08fc |
| 90-minute maximum | 3.4fc |
| Emergency fixtures | 5 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 10W |
| Apparent input per fixture | 13VA |
| Battery system voltage | 12 V DC |
| Inverter efficiency | 0.88 |
| Battery aging / temperature factor | 1.25× |
Results
| Initial avg. | 1.25fc |
|---|---|
| 90-min avg. | 0.71fc |
| Worst max:min | 42.5:1 |
| Battery bank | 8.88Ah |
| Walking surface area | 190ft² |
| Total initial fixture output | 4,750lm |
| Emitted flux per floor area | 25lm/ft² |
| Initial minimum | 0.15fc |
| Initial maximum | 2.8fc |
| Initial max / min | 18.67:1 |
| 90-minute minimum | 0.08fc |
| 90-minute maximum | 3.4fc |
| 90-minute max / min | 42.5:1 |
| Inverter real load | 50W |
| Inverter apparent load | 65VA |
| Assumed fixture power factor | 0.769 |
| Estimated DC current | 4.73A |
| DC energy before derating | 85.23Wh |
NFPA 101 egress screen
- Initial mean · 1.25 / ≥ 1 fc · Within screen
- Initial minimum · 0.15 / ≥ 0.1 fc · Within screen
- 90-minute mean · 0.71 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.08 / ≥ 0.06 fc · Within screen
- Initial max / min · 18.667 / ≤ 40 :1 · Within screen
- 90-minute max / min · 42.5 / ≤ 40 :1 · Outside screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.