Corridor with a dark point
Keep the mean above the initial threshold while setting the darkest point to zero. The minimum and uniformity checks fail despite the higher mean.
Inputs
View results ↑- Initial avg.
- 1.4fc
- 90-min avg.
- 1.12fc
- Worst max:min
- —
- Battery bank
- 8.52Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Review needed- Initial mean1.4 / ≥ 1 fc within screen
- Initial minimum0 / ≥ 0.1 fc outside screen
- 90-minute mean1.12 / ≥ 0.6 fc within screen
- 90-minute minimum0 / ≥ 0.06 fc outside screen
- Initial max / min— / ≤ 40 :1 outside screen
- 90-minute max / min— / ≤ 40 :1 outside screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 576ft² |
|---|---|
| Total initial fixture output | 9,120lm |
| Emitted flux per floor area | 15.83lm/ft² |
| Initial minimum | 0fc |
| Initial maximum | 3.4fc |
| Initial max / min | — |
| 90-minute minimum | 0fc |
| 90-minute maximum | 2.72fc |
| 90-minute max / min | — |
| Inverter real load | 96W |
| Inverter apparent load | 120VA |
| Assumed fixture power factor | 0.8 |
| Estimated DC current | 4.55A |
| DC energy before derating | 163.64Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1.4 fc and 0 fc. The corresponding 90-minute values are 1.12 fc and 0 fc.
- A zero minimum fails the uniformity check.
- The inverter supplies 120 VA and 96 W. For 90 minutes, the estimated derated bank is 8.52 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Corridor with a dark point
Inputs
| Egress path length | 96ft |
|---|---|
| Path clear width | 6ft |
| Initial average | 1.4fc |
| Initial minimum | 0fc |
| Initial maximum | 3.4fc |
| 90-minute readings | Apply output retention factor |
| End-of-discharge retention | 0.8 |
| Emergency fixtures | 8 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 12W |
| Apparent input per fixture | 15VA |
| Battery system voltage | 24 V DC |
| Inverter efficiency | 0.88 |
| Battery aging / temperature factor | 1.25× |
Results
| Initial avg. | 1.4fc |
|---|---|
| 90-min avg. | 1.12fc |
| Worst max:min | — |
| Battery bank | 8.52Ah |
| Walking surface area | 576ft² |
| Total initial fixture output | 9,120lm |
| Emitted flux per floor area | 15.83lm/ft² |
| Initial minimum | 0fc |
| Initial maximum | 3.4fc |
| Initial max / min | — |
| 90-minute minimum | 0fc |
| 90-minute maximum | 2.72fc |
| 90-minute max / min | — |
| Inverter real load | 96W |
| Inverter apparent load | 120VA |
| Assumed fixture power factor | 0.8 |
| Estimated DC current | 4.55A |
| DC energy before derating | 163.64Wh |
NFPA 101 egress screen
- Initial mean · 1.4 / ≥ 1 fc · Within screen
- Initial minimum · 0 / ≥ 0.1 fc · Outside screen
- 90-minute mean · 1.12 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0 / ≥ 0.06 fc · Outside screen
- Initial max / min · — / ≤ 40 :1 · Outside screen
- 90-minute max / min · — / ≤ 40 :1 · Outside screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.