At the NFPA screening limits

Use the initial and final minimum/mean floors and an initial maximum-to-minimum ratio of exactly 40:1.

Path and initial readings
ft
ft
fc
fc
fc
fc
fc
fc
Emergency circuit and inverter
lm/W
W
VA
×
Initial avg.
1fc
90-min avg.
0.6fc
Worst max:min
40:1
Battery bank
9.59Ah

Initial and 90-minute path light levels

Edit inputs ↓
Initial and 90-minute path light levelsEGRESS FLOOR LEVELSURVEY RANGESInitial surveyavg 1 fc90-minute surveyavg 0.6 fcPath 96 ft40:1 limitWorst uniformity40:1
Markers show the minimum, mean and maximum for the entered survey. The ranges do not assign values to specific points on the path.

NFPA 101 egress screen

Within screen
OutsideThresholdWithin
  • Initial mean1 / ≥ 1 fc within screen
  • Initial minimum0.1 / ≥ 0.1 fc within screen
  • 90-minute mean0.6 / ≥ 0.6 fc within screen
  • 90-minute minimum0.06 / ≥ 0.06 fc within screen
  • Initial max / min40 / ≤ 40 :1 within screen
  • 90-minute max / min40 / ≤ 40 :1 within screen

The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.

Additional readings
Walking surface area576ft²
Total initial fixture output5,130lm
Emitted flux per floor area8.91lm/ft²
Initial minimum0.1fc
Initial maximum4fc
Initial max / min40:1
90-minute minimum0.06fc
90-minute maximum2.4fc
90-minute max / min40:1
Inverter real load54W
Inverter apparent load72VA
Assumed fixture power factor0.75
Estimated DC current5.11A
DC energy before derating92.05Wh

Worked calculation

US customary results for the original preset.

  1. The initial average and minimum are 1 fc and 0.1 fc. The corresponding 90-minute values are 0.6 fc and 0.06 fc.
  2. The worst maximum-to-minimum ratio is 40:1 against the 40:1 limit.
  3. The inverter supplies 72 VA and 54 W. For 90 minutes, the estimated derated bank is 9.59 Ah.

Calculation method

Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.

NFPA 101 screening floors
Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
Uniformity at both times
Emax/Emin ≤ 40:1 · a zero minimum fails the screen
Inverter and battery
VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)

Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.

Sources and assumptions ↗