Regulated emergency inverter output

Use a constant-output driver and a higher inverter efficiency. The modeled 90-minute photometry matches the initial survey.

Path and initial readings
ft
ft
fc
fc
fc
Emergency circuit and inverter
lm/W
W
VA
×
Initial avg.
1.48fc
90-min avg.
1.48fc
Worst max:min
20:1
Battery bank
10.11Ah

Initial and 90-minute path light levels

Edit inputs ↓
Initial and 90-minute path light levelsEGRESS FLOOR LEVELSURVEY RANGESInitial surveyavg 1.48 fc90-minute surveyavg 1.48 fcPath 68 ft40:1 limitWorst uniformity20:1
Markers show the minimum, mean and maximum for the entered survey. The ranges do not assign values to specific points on the path.

NFPA 101 egress screen

Within screen
OutsideThresholdWithin
  • Initial mean1.48 / ≥ 1 fc within screen
  • Initial minimum0.24 / ≥ 0.1 fc within screen
  • 90-minute mean1.48 / ≥ 0.6 fc within screen
  • 90-minute minimum0.24 / ≥ 0.06 fc within screen
  • Initial max / min20 / ≤ 40 :1 within screen
  • 90-minute max / min20 / ≤ 40 :1 within screen

The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.

Additional readings
Walking surface area408ft²
Total initial fixture output11,115lm
Emitted flux per floor area27.24lm/ft²
Initial minimum0.24fc
Initial maximum4.8fc
Initial max / min20:1
90-minute minimum0.24fc
90-minute maximum4.8fc
90-minute max / min20:1
Inverter real load117W
Inverter apparent load135VA
Assumed fixture power factor0.867
Estimated DC current5.19A
DC energy before derating186.7Wh

Worked calculation

US customary results for the original preset.

  1. The initial average and minimum are 1.48 fc and 0.24 fc. The corresponding 90-minute values are 1.48 fc and 0.24 fc.
  2. The worst maximum-to-minimum ratio is 20:1 against the 40:1 limit.
  3. The inverter supplies 135 VA and 117 W. For 90 minutes, the estimated derated bank is 10.11 Ah.

Calculation method

Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.

NFPA 101 screening floors
Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
Uniformity at both times
Emax/Emin ≤ 40:1 · a zero minimum fails the screen
Inverter and battery
VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)

Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.