Regulated emergency inverter output
Use a constant-output driver and a higher inverter efficiency. The modeled 90-minute photometry matches the initial survey.
Inputs
View results ↑- Initial avg.
- 1.48fc
- 90-min avg.
- 1.48fc
- Worst max:min
- 20:1
- Battery bank
- 10.11Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Within screen- Initial mean1.48 / ≥ 1 fc within screen
- Initial minimum0.24 / ≥ 0.1 fc within screen
- 90-minute mean1.48 / ≥ 0.6 fc within screen
- 90-minute minimum0.24 / ≥ 0.06 fc within screen
- Initial max / min20 / ≤ 40 :1 within screen
- 90-minute max / min20 / ≤ 40 :1 within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 408ft² |
|---|---|
| Total initial fixture output | 11,115lm |
| Emitted flux per floor area | 27.24lm/ft² |
| Initial minimum | 0.24fc |
| Initial maximum | 4.8fc |
| Initial max / min | 20:1 |
| 90-minute minimum | 0.24fc |
| 90-minute maximum | 4.8fc |
| 90-minute max / min | 20:1 |
| Inverter real load | 117W |
| Inverter apparent load | 135VA |
| Assumed fixture power factor | 0.867 |
| Estimated DC current | 5.19A |
| DC energy before derating | 186.7Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1.48 fc and 0.24 fc. The corresponding 90-minute values are 1.48 fc and 0.24 fc.
- The worst maximum-to-minimum ratio is 20:1 against the 40:1 limit.
- The inverter supplies 135 VA and 117 W. For 90 minutes, the estimated derated bank is 10.11 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗Regulated emergency inverter output
Inputs
| Egress path length | 68ft |
|---|---|
| Path clear width | 6ft |
| Initial average | 1.48fc |
| Initial minimum | 0.24fc |
| Initial maximum | 4.8fc |
| 90-minute readings | Apply output retention factor |
| End-of-discharge retention | 1 |
| Emergency fixtures | 9 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 13W |
| Apparent input per fixture | 15VA |
| Battery system voltage | 24 V DC |
| Inverter efficiency | 0.94 |
| Battery aging / temperature factor | 1.3× |
Results
| Initial avg. | 1.48fc |
|---|---|
| 90-min avg. | 1.48fc |
| Worst max:min | 20:1 |
| Battery bank | 10.11Ah |
| Walking surface area | 408ft² |
| Total initial fixture output | 11,115lm |
| Emitted flux per floor area | 27.24lm/ft² |
| Initial minimum | 0.24fc |
| Initial maximum | 4.8fc |
| Initial max / min | 20:1 |
| 90-minute minimum | 0.24fc |
| 90-minute maximum | 4.8fc |
| 90-minute max / min | 20:1 |
| Inverter real load | 117W |
| Inverter apparent load | 135VA |
| Assumed fixture power factor | 0.867 |
| Estimated DC current | 5.19A |
| DC energy before derating | 186.7Wh |
NFPA 101 egress screen
- Initial mean · 1.48 / ≥ 1 fc · Within screen
- Initial minimum · 0.24 / ≥ 0.1 fc · Within screen
- 90-minute mean · 1.48 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.24 / ≥ 0.06 fc · Within screen
- Initial max / min · 20 / ≤ 40 :1 · Within screen
- 90-minute max / min · 20 / ≤ 40 :1 · Within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.