Corridor with a dark point

Keep the mean above the initial threshold while setting the darkest point to zero. The minimum and uniformity checks fail despite the higher mean.

Path and initial readings
ft
ft
fc
fc
fc
Emergency circuit and inverter
lm/W
W
VA
×
Initial avg.
1.4fc
90-min avg.
1.12fc
Worst max:min
—
Battery bank
8.52Ah

Initial and 90-minute path light levels

Edit inputs ↓
Initial and 90-minute path light levelsEGRESS FLOOR LEVELSURVEY RANGESInitial surveyavg 1.4 fc90-minute surveyavg 1.12 fcPath 96 ft40:1 limitWorst uniformityNo finite ratio
Markers show the minimum, mean and maximum for the entered survey. The ranges do not assign values to specific points on the path.

NFPA 101 egress screen

Review needed
OutsideThresholdWithin
  • Initial mean1.4 / ≥ 1 fc within screen
  • Initial minimum0 / ≥ 0.1 fc outside screen
  • 90-minute mean1.12 / ≥ 0.6 fc within screen
  • 90-minute minimum0 / ≥ 0.06 fc outside screen
  • Initial max / min— / ≤ 40 :1 outside screen
  • 90-minute max / min— / ≤ 40 :1 outside screen

The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.

Additional readings
Walking surface area576ft²
Total initial fixture output9,120lm
Emitted flux per floor area15.83lm/ft²
Initial minimum0fc
Initial maximum3.4fc
Initial max / min—
90-minute minimum0fc
90-minute maximum2.72fc
90-minute max / min—
Inverter real load96W
Inverter apparent load120VA
Assumed fixture power factor0.8
Estimated DC current4.55A
DC energy before derating163.64Wh

Worked calculation

US customary results for the original preset.

  1. The initial average and minimum are 1.4 fc and 0 fc. The corresponding 90-minute values are 1.12 fc and 0 fc.
  2. A zero minimum fails the uniformity check.
  3. The inverter supplies 120 VA and 96 W. For 90 minutes, the estimated derated bank is 8.52 Ah.

Calculation method

Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.

NFPA 101 screening floors
Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
Uniformity at both times
Emax/Emin ≤ 40:1 · a zero minimum fails the screen
Inverter and battery
VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)

Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.