At the NFPA screening limits
Use the initial and final minimum/mean floors and an initial maximum-to-minimum ratio of exactly 40:1.
Inputs
View results ↑- Initial avg.
- 1fc
- 90-min avg.
- 0.6fc
- Worst max:min
- 40:1
- Battery bank
- 9.59Ah
Initial and 90-minute path light levels
Edit inputs ↓NFPA 101 egress screen
Within screen- Initial mean1 / ≥ 1 fc within screen
- Initial minimum0.1 / ≥ 0.1 fc within screen
- 90-minute mean0.6 / ≥ 0.6 fc within screen
- 90-minute minimum0.06 / ≥ 0.06 fc within screen
- Initial max / min40 / ≤ 40 :1 within screen
- 90-minute max / min40 / ≤ 40 :1 within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Additional readings
| Walking surface area | 576ft² |
|---|---|
| Total initial fixture output | 5,130lm |
| Emitted flux per floor area | 8.91lm/ft² |
| Initial minimum | 0.1fc |
| Initial maximum | 4fc |
| Initial max / min | 40:1 |
| 90-minute minimum | 0.06fc |
| 90-minute maximum | 2.4fc |
| 90-minute max / min | 40:1 |
| Inverter real load | 54W |
| Inverter apparent load | 72VA |
| Assumed fixture power factor | 0.75 |
| Estimated DC current | 5.11A |
| DC energy before derating | 92.05Wh |
Worked calculation
US customary results for the original preset.
- The initial average and minimum are 1 fc and 0.1 fc. The corresponding 90-minute values are 0.6 fc and 0.06 fc.
- The worst maximum-to-minimum ratio is 40:1 against the 40:1 limit.
- The inverter supplies 72 VA and 54 W. For 90 minutes, the estimated derated bank is 9.59 Ah.
Calculation method
Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.
- NFPA 101 screening floors
- Initial avg ≥ 1 fc, min ≥ 0.1 fc · At 90 min avg ≥ 0.6 fc, min ≥ 0.06 fc
- Uniformity at both times
- Emax/Emin ≤ 40:1 · a zero minimum fails the screen
- Inverter and battery
- VAload = count × VA per fixture · Ah = Wload × 1.5 h × derating/(VDC × η)
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.
Sources and assumptions ↗At the NFPA screening limits
Inputs
| Egress path length | 96ft |
|---|---|
| Path clear width | 6ft |
| Initial average | 1fc |
| Initial minimum | 0.1fc |
| Initial maximum | 4fc |
| 90-minute readings | Enter measured or modeled readings |
| 90-minute average | 0.6fc |
| 90-minute minimum | 0.06fc |
| 90-minute maximum | 2.4fc |
| Emergency fixtures | 6 |
| Initial fixture efficacy | 95lm/W |
| Real input per fixture | 9W |
| Apparent input per fixture | 12VA |
| Battery system voltage | 12 V DC |
| Inverter efficiency | 0.88 |
| Battery aging / temperature factor | 1.25× |
Results
| Initial avg. | 1fc |
|---|---|
| 90-min avg. | 0.6fc |
| Worst max:min | 40:1 |
| Battery bank | 9.59Ah |
| Walking surface area | 576ft² |
| Total initial fixture output | 5,130lm |
| Emitted flux per floor area | 8.91lm/ft² |
| Initial minimum | 0.1fc |
| Initial maximum | 4fc |
| Initial max / min | 40:1 |
| 90-minute minimum | 0.06fc |
| 90-minute maximum | 2.4fc |
| 90-minute max / min | 40:1 |
| Inverter real load | 54W |
| Inverter apparent load | 72VA |
| Assumed fixture power factor | 0.75 |
| Estimated DC current | 5.11A |
| DC energy before derating | 92.05Wh |
NFPA 101 egress screen
- Initial mean · 1 / ≥ 1 fc · Within screen
- Initial minimum · 0.1 / ≥ 0.1 fc · Within screen
- 90-minute mean · 0.6 / ≥ 0.6 fc · Within screen
- 90-minute minimum · 0.06 / ≥ 0.06 fc · Within screen
- Initial max / min · 40 / ≤ 40 :1 · Within screen
- 90-minute max / min · 40 / ≤ 40 :1 · Within screen
The 90-minute light floors are 60% of the initial code floors. The 40:1 limit applies to both readings.
Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.