Long hotel service corridor

Test whether the low fixture count from the lumen budget also keeps the spacing acceptable in a narrow corridor.

Room geometry
ft
ft
ft
ft
ft
Luminaire and target
lm
fc
×
W
Fixture grid
6 × 1
Maintained
8.75fc
Cavity ratio
6.98
Connected
132W

Room section and fixture plan

Edit inputs ↓
Room section and fixture planROOM SECTIONFIXTURE PLANCavity 9 ft6 × 1 GRIDMaintained workplane8.75 fc
The grid uses equal pitch with half-pitch offsets at the walls.

IES layout screen

Review needed
OutsideThresholdWithin
  • Maintained target8.75 / ≥ 8 fc within screen
  • Spacing / mounting height1.52 / ≤ 1.1 × outside screen

Checks compare maintained average and the entered spacing criterion.

Additional readings
Floor area574ft²
Room cavity height9ft
Combined light loss factor0.7585
Maintained lumens per fixture837.41lm
Calculated fractional fixture count5.4836
Minimum whole fixture count6
Fixtures in rectangular grid6
Lengthwise pitch13.67ft
Crosswise pitch7ft
Largest pitch / mounting height1.519×
Pitch limit from spacing criterion9.9ft

Worked calculation

US customary results for the original preset.

  1. Use the room section to get a cavity height of 9 ft and an RCR of 6.977.
  2. Multiply 2300 lm by CU 0.48 and LLF 0.7585 to get 837.41 lm maintained per fixture.
  3. Round 5.4836 up to 6. The 6 × 1 grid supplies 8.75 fc on average.

Calculation method

Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.

Room cavity ratio
hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
Maintained lumens per fixture
Φmaintained = Φ × CU × LLD × LDD × BF
Fixture count and pitch
N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny

Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.

Sources and assumptions ↗