Open-plan design studio
Lay out broad-distribution fixtures over a drawing and model-making studio. The spacing check uses the luminaire’s published criterion.
Inputs
View results ↑- Fixture grid
- 7 × 3
- Maintained
- 47.79fc
- Cavity ratio
- 2.82
- Connected
- 714W
Room section and fixture plan
Edit inputs ↓IES layout screen
Within screen- Maintained target47.79 / ≥ 45 fc within screen
- Spacing / mounting height0.91 / ≤ 1.35 × within screen
Checks compare maintained average and the entered spacing criterion.
Additional readings
| Floor area | 1,248ft² |
|---|---|
| Room cavity height | 9.5ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 2,839.9lm |
| Calculated fractional fixture count | 19.7754 |
| Minimum whole fixture count | 20 |
| Fixtures in rectangular grid | 21 |
| Lengthwise pitch | 6.86ft |
| Crosswise pitch | 8.67ft |
| Largest pitch / mounting height | 0.912× |
| Pitch limit from spacing criterion | 12.83ft |
Worked calculation
US customary results for the original preset.
- Use the room section to get a cavity height of 9.5 ft and an RCR of 2.817.
- Multiply 5200 lm by CU 0.72 and LLF 0.7585 to get 2839.9 lm maintained per fixture.
- Round 19.7754 up to 20. The 7 × 3 grid supplies 47.79 fc on average.
Calculation method
Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.
- Room cavity ratio
- hᵣ꜀ = H − hwp − hcc · RCR = 5hᵣ꜀(L + W)/(LW)
- Maintained lumens per fixture
- Φmaintained = Φ × CU × LLD × LDD × BF
- Fixture count and pitch
- N = Etarget × LW/Φmaintained · Sx = L/Nx · Sy = W/Ny
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.
Sources and assumptions ↗Open-plan design studio
Inputs
| Room length | 48ft |
|---|---|
| Room width | 26ft |
| Ceiling height | 13ft |
| Workplane height | 3ft |
| Fixture suspension | 0.5ft |
| Output per fixture | 5,200lm |
| Utilization (CU) | 0.72 |
| Lumen depreciation (LLD) | 0.9 |
| Dirt depreciation (LDD) | 0.86 |
| Ballast factor (BF) | 0.98 |
| Target illuminance | 45fc |
| Max spacing / height | 1.35× |
| Input per fixture | 34W |
Results
| Fixture grid | 7 × 3 |
|---|---|
| Maintained | 47.79fc |
| Cavity ratio | 2.82 |
| Connected | 714W |
| Floor area | 1,248ft² |
| Room cavity height | 9.5ft |
| Combined light loss factor | 0.7585 |
| Maintained lumens per fixture | 2,839.9lm |
| Calculated fractional fixture count | 19.7754 |
| Minimum whole fixture count | 20 |
| Fixtures in rectangular grid | 21 |
| Lengthwise pitch | 6.86ft |
| Crosswise pitch | 8.67ft |
| Largest pitch / mounting height | 0.912× |
| Pitch limit from spacing criterion | 12.83ft |
IES layout screen
- Maintained target · 47.79 / ≥ 45 fc · Within screen
- Spacing / mounting height · 0.91 / ≤ 1.35 × · Within screen
Checks compare maintained average and the entered spacing criterion.
Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.