Worked calculation
The floor is 576 kW, which already exceeds the baseline 420 kW. Reducing the measured peak by 80 kW cannot lower this month’s demand charge.
- Historical ratchet floor
- 576 kW
- Billed demand before
- 576 kW
- Monthly demand savings
- 0 USD/mo
Values in this solution use the original example inputs.
Formulas & assumptions
A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.