Peak reduction without a ratchet

A production facility uses 215,000 kWh over 30 days with a 780 kW peak and no demand ratchet.

Inputs

Metered month
Tariff inputs

Load duration and billed demand

60 Hz · US customaryEdit inputs
Load duration and billed demand at 60 Hz LOAD FACTOR38.28%BILLED PEAK780kWDEMAND SHARE35.31%MONTH SAVED2.24KUSD/moIllustrative load durationPeak 780 kWStart100% of hoursPeak-shaving bill impactBilled before780 kWBilled after620 kWRatchet floor0 kWLoad factor38.3%100% flat

Detailed results
Billing hours
720 h
Average metered demand
298.61 kW
Monthly load factor
38.28%
Historical ratchet floor
0 kW
Billed demand before
780 kW
Metered peak after
620 kW
Billed demand after
620 kW
Effective metered reduction
160 kW
Baseline energy charge
19,780 USD
Baseline demand charge
10,920 USD
Demand share of modeled bill
35.31%
Baseline monthly bill
30,925 USD
Modeled bill after shaving
28,685 USD
Baseline blended rate
0.1438 USD/kWh
Monthly demand savings
2,240 USD/mo
Annual savings at identical months
26,880 USD/yr

Worked calculation

A 160 kW shave reduces both the metered and billed peak to 620 kW. The rate is 14 USD/kW, so all 160 kW produces a demand saving.

Billed demand after
620 kW
Monthly demand savings
2,240 USD/mo
Annual savings at identical months
26,880 USD/yr

Values in this solution use the original example inputs.

Formulas & assumptions

Monthly load factor

Load factor = kWh / (15-minute kW_peak · 24 · billing days)

Enter gross import kWh and the 15-minute measured peak from the same billing period. One interval at peak consumes 0.25 × peak kWh. The load factor is unavailable when the measured peak is zero.

Demand ratchet

kW_billed = max(kW_peak, historical peak · ratchet fraction)

Use the utility’s historical billing window and demand interval. Apply the same ratchet floor before and after shaving. With energy held constant, modeled peak cannot drop below average demand.

Energy, demand and savings

Bill = kWh · energy tariff + billed kW · demand tariff + fixed charge

Divide the baseline bill by kWh for the effective rate. Multiply the decrease in billed kW by the demand tariff to find monthly savings. Annual savings assumes twelve identical months.

A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.

Engineering references

More worked examples