Engineering methodology

Electrical assumptions and reference material for the eight calculators.

Shared conventions

Voltages and currents are RMS. Three-phase tools use line-to-line voltage and a balanced positive-sequence network unless the selected case explicitly models a neutral. The 50/60 Hz setting changes frequency-dependent quantities. Use voltages and equipment data for the frequency selected.

US/Metric switches convert dimensions, shaft ratings, ambient temperature, liquid fuel, and impedance quantities when applicable. Calculations retain their original physical inputs when toggled. Gas consumption is standard cubic volume per hour. Currency selections label entries without an exchange-rate conversion.

Three-phase power

Sinusoidal steady-state RMS with L1–L2–L3 positive sequence. The phasor arrows are line currents on an ideal phase reference. Delta winding current follows the magnitude relation shown above.

Power factor correction

Balanced sinusoidal load. Compare manufacturer voltage, step size, inrush and switching duties. Review harmonics, resonance, and light-load overcompensation before choosing a bank.

Distribution transformer

Nominal RMS voltages, symmetric bolted fault at secondary terminals, and losses at a fixed reference temperature. Check source X/R, service voltage, impedance tolerance, downstream impedance, and contributions from motors and generators in a fault study.

Induction motor starting

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.

Standby generator

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.

Feeder voltage drop

Balanced three-phase lagging load. The effective R/X model omits installation-specific spacing and heating. The 0.01–5 s adiabatic screen requires conductor and termination checks. For current-limiting devices, use published let-through I²t and verify coordination.

Harmonic distortion

Equal phase spectra with balanced sequence and sinusoidal voltage. The displayed THD-I describes the entered current spectrum. IEEE 519 limits are assessed at the point of common coupling with the applicable quantities, including TDD. Transformer thermal loading also depends on construction and rated current.

Utility demand charges

A flat energy rate and one non-coincident demand charge, with optional look-back ratchet and fixed fee. Use the actual utility bill and interval data for time-of-use periods, coincident peaks, power-factor charges or seasonal ratchets.