- Required standby nameplate power
- 301.39 kW
- Required standby nameplate capacity
- 376.74 kVA
- Available capacity factor
- 88.92%
- Elevation derating
- 9.45%
- Temperature derating
- 1.8%
- Pre-step running apparent power
- 225 kVA
- Modeled pickup apparent power
- 335 kVA
- Modeled pickup real power
- 218.5 kW
- Available standby power at site
- 268 kW
- Available standby capacity at site
- 335 kVA
- Running load on nameplate
- 59.72%
- Fuel rate at running load
- 13.51 gal/h
- Fuel rate at 25% of nameplate
- 7.23 gal/h
- Fuel rate at 50% of nameplate
- 11.75 gal/h
- Fuel rate at 75% of nameplate
- 16.28 gal/h
- Fuel rate at 100% of nameplate
- 21.1 gal/h
- Usable diesel volume
- 225 gal
- Estimated diesel runtime
- 16.65 h