- Required standby nameplate power
- 248.7 kW
- Required standby nameplate capacity
- 310.88 kVA
- Available capacity factor
- 96.5%
- Elevation derating
- 0%
- Temperature derating
- 3.5%
- Pre-step running apparent power
- 260.87 kVA
- Modeled pickup apparent power
- 260.87 kVA
- Modeled pickup real power
- 240 kW
- Available standby power at site
- 240 kW
- Available standby capacity at site
- 300 kVA
- Running load on nameplate
- 96.5%
- Fuel rate at running load
- 16.85 gal/h
- Fuel rate at 25% of nameplate
- 5.97 gal/h
- Fuel rate at 50% of nameplate
- 9.7 gal/h
- Fuel rate at 75% of nameplate
- 13.43 gal/h
- Fuel rate at 100% of nameplate
- 17.41 gal/h
- Usable diesel volume
- 288 gal
- Estimated diesel runtime
- 17.09 h