Hot-site steady standby load

A process station at 112 °F and 300 ft has 240 kW steady load at 0.92 PF and no motor step.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

60 Hz · US customaryEdit inputs
Load pickup and fuel consumption at 60 Hz STANDBY KW248.7kWSTANDBY KVA310.88kVASITE CAPACITY96.5%TANK RUNTIME17.09hModeled load stepSite limit 300 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWTank17.1 hSite rating96.5% retained100% rated

Detailed results
Required standby nameplate power
248.7 kW
Required standby nameplate capacity
310.88 kVA
Available capacity factor
96.5%
Elevation derating
0%
Temperature derating
3.5%
Pre-step running apparent power
260.87 kVA
Modeled pickup apparent power
260.87 kVA
Modeled pickup real power
240 kW
Available standby power at site
240 kW
Available standby capacity at site
300 kVA
Running load on nameplate
96.5%
Fuel rate at running load
16.85 gal/h
Fuel rate at 25% of nameplate
5.97 gal/h
Fuel rate at 50% of nameplate
9.7 gal/h
Fuel rate at 75% of nameplate
13.43 gal/h
Fuel rate at 100% of nameplate
17.41 gal/h
Usable diesel volume
288 gal
Estimated diesel runtime
17.09 h

Worked calculation

The temperature loss is (112 − 77)·0.001 = 3.5%, and the elevation contributes no derate. At 0.8 generator PF the steady kW requirement controls sizing.

Temperature derating
3.5%
Required standby nameplate power
248.7 kW
Required standby nameplate capacity
310.88 kVA

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.